The Eaton Bussmann Low-Peak LPJ-600SPI is a 600A indicating UL Class J fuse with dual-element, current-limiting and time-delay performance. It provides a minimum 10-second operating time at 500% of rated current and a 300kA RMS symmetrical interrupting rating at 600VAC. The easyID open-fuse indicator requires at least 75VAC, and this indicating version is not DC rated.
Quick answer, specifications & FAQ
Direct answer
Eaton Bussmann Current-Limiting Dual-Element Branch-Circuit Fuse LPJ-600SPI is rated 600A, 600V AC, Time Delay. Breaking capacity 300kA RMS symmetrical at 600VAC, I²t See official current-limitation curves, certifications cULus Listed (JDDZ.E4273) · CSA Certified · CE · RoHS Compliant. Listed applications: Branch Circuit Protection, Industrial Control Protection, Motor protection, Power Distribution Protection. Standards: CSA C22.2 No. 248.8, UL 248-8. 600A Low-Peak Class J dual-element time-delay fuse, indicating, rated 600VAC.
Last updated 23 days ago
Key specifications
- Part number: LPJ-600SPI
- Brand: Eaton Bussmann
- Rated current: 600A
- Rated voltage: 600V AC
- Breaking capacity: 300kA RMS symmetrical at 600VAC
- Fuse speed: Time Delay
- Dimensions: Drawing dimensions: 8.00 / 6.00 / 3.75 in reference lengths; 2.50 in body diameter; terminal details 0.53 / 0.69 / 2.13 / 2.00 / 0.38 in
- Terminal type: Class J blade terminals
- Certifications: cULus Listed (JDDZ.E4273) · CSA Certified · CE · RoHS Compliant
- Standards: CSA C22.2 No. 248.8, UL 248-8
- Typical lead time: 8-12 weeks
- Fuse indicator: Indicating easyID; minimum indicator voltage 75VAC; indicating version is not DC rated; Response: minimum 10 s at 500% rated current; Carton quantity: 1; Recommended JM fuse blocks: JM60600-1CR, JM60600-2CR, JM60600-3CR. Source: Eaton Technical Data 1007, July 2023.
Frequently asked questions
What are the current and voltage ratings of LPJ-600SPI?
LPJ-600SPI is rated 600A at 600V AC.
What is the breaking capacity of LPJ-600SPI?
LPJ-600SPI has a breaking capacity of 300kA RMS symmetrical at 600VAC. Confirm this covers the available fault current at the installation point.
Which standards and approvals apply to LPJ-600SPI?
LPJ-600SPI is listed under CSA C22.2 No. 248.8, UL 248-8 / cULus Listed (JDDZ.E4273) · CSA Certified · CE · RoHS Compliant.
What is LPJ-600SPI used for?
LPJ-600SPI is listed for Branch Circuit Protection, Industrial Control Protection, Motor protection, Power Distribution Protection applications. Verify suitability for your circuit before ordering.
What are the ordering terms for LPJ-600SPI?
LPJ-600SPI: typical lead time 8-12 weeks. Submit a quote request for a firm quotation.
Data sources
- Part number
- LPJ-600SPI
- Brand
- Eaton Bussmann
- Last updated
- 2026-10-10
- Canonical URL
- https://fusestock.com/products/lpj-600spi-eaton-bussmann/
Technical Specifications
- Part Number
- LPJ-600SPI
- Manufacturer Part Number
- LPJ-600SPI
- Series
- Low-Peak LPJ Class J
- Fuse Type
- Current-Limiting Dual-Element Branch-Circuit Fuse
- Current Rating
- 600A
- Voltage Rating
- 600V AC
- AC / DC
- AC
- Breaking Capacity
- 300kA RMS symmetrical at 600VAC
- I²t
- See official current-limitation curves
- Package / Dimensions
- Drawing dimensions: 8.00 / 6.00 / 3.75 in reference lengths; 2.50 in body diameter; terminal details 0.53 / 0.69 / 2.13 / 2.00 / 0.38 in
- Mounting
- Bolt Mount
- Application
- Branch Circuit Protection · Industrial Control Protection · Motor protection · Power Distribution Protection
- Standard
- CSA C22.2 No. 248.8 · UL 248-8
- Terminal Type
- Class J blade terminals
- Fuse Speed
- Time Delay
- Utilization Class
- Class J
- Approvals
- CE · CSA Approval (Unspecified) · cULus · RoHS
- Certifications
- cULus Listed (JDDZ.E4273) · CSA Certified · CE · RoHS Compliant
- Reference Lead Time
- 8-12 weeks
- Fuse indicator
- Indicating easyID; minimum indicator voltage 75VAC; indicating version is not DC rated; Response: minimum 10 s at 500% rated current; Carton quantity: 1; Recommended JM fuse blocks: JM60600-1CR, JM60600-2CR, JM60600-3CR. Source: Eaton Technical Data 1007, July 2023.