Designed within Mersen’s ATMR Series, ATMR9 carries a 9A rating and Class CC form factor. Electrical limits are 600V AC / 600V DC, with 200kA AC / 100kA DC interrupting capability. The protection profile emphasizes fast-acting rejection-style Class CC protection for control and branch circuits. Mechanically, it follows the Class CC form factor and ferrule terminal style for clip-mounted fuse installations. Typical selection contexts include Branch Circuit Protection, Control Circuits, Lighting. For design release, confirm coordination, dimensions and approval details in the official Mersen documentation.
Technical Specifications
- Part Number
- ATMR9
- Manufacturer Part Number
- ATMR9
- Series
- ATMR Series
- Fuse Type
- Current-Limiting Fast-Acting Class CC Fuse
- Current Rating
- 9A
- Voltage Rating
- 600V AC / 600V DC
- AC / DC
- AC/DC
- Breaking Capacity
- 200kA AC / 100kA DC
- Package / Dimensions
- Class CC
- Mounting
- Cartridge / Clip
- Application
- Branch Circuit Protection · Control circuits · General Loads · Lighting
- Standard
- CSA C22.2 No. 248.4 · UL 248-4
- Terminal Type
- Ferrule
- Fuse Speed
- Fast Acting
- Utilization Class
- Class CC
- Approvals
- CSA · UL Listed
- Certifications
- UL Listed · CSA